Home Search Pollutants About the Database


ExxonMobil, Baton Rouge

LDEQ Incident Report

Incident #112606
PDF AvailablePDF
State Police #509-0408
Incident Date2009-02-08
Report Date 2009-02-16
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Polycyclic Aromatic HydrocarbonsNo Information GivenCoker Feed Pump: P-6NONOYES3.6 pounds
OilNo Information GivenCoker Feed Pump: P-6NONONO121.8 pounds
NaphthaleneNo Information GivenCoker Feed Pump: P-6NONOYESBRQ

Cause of Problem: Equipment Failure

Leak occurred because a stream of cold feed entered the suction of the pump. When the cold stream reached the pump, the pump began to cavitate, causing excess vibration. The vibration caused a line coming off of the pump to break.

Discharge Preventable - Yes

Notes/Remedial Actions

The failed piping will be replaced with an upgraded class to withstand future upsets of this nature. Contaminated soil has been remediated and disposed of properly.