| LDEQ Incident Number Incident Date |
Point Source(s) | Notes | Amount of Release |
| 121796 2010-02-27 | No Information Given | Cause: COLD WEATHER. Broken line, possibly due to recent freeze but still under investigation, no info given as to where line is located. Followup: No Notes: BRQ. LDEQ reports states that based on analytical results, no reportable quantities were exceeded. Took sample of spilled material for analysis. No info given as to actual time duration of leak, only discovery time and time secured. LDEQ and State Police reports only. No refinery letter required - courtesy notification. | 10.0 gallons |
| 140561 2012-06-16 | Flange on the Pitch Exchanger 210-1317-08 North Ground Flare | Cause: Chain of Events:
The 210-1513-01 Vacuum Bottoms Pump inboard and outboard motor bearing housings were smoking during routine observations. The 210-1513-02 Vacuum Bottoms Pump (back-up) was already out of service for repairs. The board operator was notified and started reducing Crude charge rate. The 210-1513-01 Vacuum Bottoms pump was shut down due to the outboard motor bearing igniting. The 210 Crude Unit shutdown procedure was initiated. The 210-1801-01 Offgas Compressor tripped due to a high level in the 210-1202 Compressor Suction Drum. Both pumps were already on in automatic. The outsider operator opened the bypass around the flow controller to the Product Receiver. Crude overhead gas was flared in the North Ground Flare. Followup: No Notes: The boardman cut charge rates to Crude Unit 10 and shut down Crude Unit 210. Both Compressor Suction Drum pumps were turned on, and the bypass around the flow controller was opened. The operator increased the suction drum pressure to assist the pumps in pressuring out the level to the startup compressor. The incident investigation will result in recommendation items designed to prevent the recurrence of this event. | 5.0 gallons |
| 137050 2012-02-07 | Unit 63 Tank Farm | Cause: The product inside the Unit 210 Crude Charge Pump caught fire due to a seal failure. While extinguishing the fire with fire water, some product spilled to the concrete containment around the tank. An incident investigation is being conducted to determine the root cause of the incident. 6-10 bbl of crude oil burned in the tank in addition to one bbl of oil released. Followup: No Notes: The pump suction and discharge were blocked in to stop the flow. The Shift Emergency Response Team (SERT) responded and extinguished the fire. A vacuum truck removed the spilled product. The oil was to be reprocessed, and the water would be treated in the waste water treatment plant. The incident investigation will result in recommendation items to prevent the recurrence of this event. There was no medical attention necessary for the exposed individuals. | 42.0 gallons |
| 137050 2012-02-07 | Unit 63 Tank Farm | Cause: The product inside the Unit 210 Crude Charge Pump caught fire due to a seal failure. While extinguishing the fire with fire water, some product spilled to the concrete containment around the tank. An incident investigation is being conducted to determine the root cause of the incident. 6-10 bbl of crude oil burned in the tank in addition to one bbl of oil released. Followup: No Notes: The pump suction and discharge were blocked in to stop the flow. The Shift Emergency Response Team (SERT) responded and extinguished the fire. A vacuum truck removed the spilled product. The oil was to be reprocessed, and the water would be treated in the waste water treatment plant. The incident investigation will result in recommendation items to prevent the recurrence of this event. There was no medical attention necessary for the exposed individuals. | 252.0 gallons |